Process Control & Safety Instrumentation  
INDUSTRIAL EQUIPMENTS
 
Industrial Home
Chemical Feed Equipment
On-Site Generation System
Process Control & Safety Instrumentation
Water Quality Monitoring Equipment
 
GF Series - 200
GFCC Series - FX4800/4900
LCV Series - 4600
SPGD Series - 1610B
MPGD Series - 1620B
CRA Series - 1870E



Capital Controls Multipoint Gas Detector Series 1620B provides continuous detection of chlorine or sulfur dioxide gas in a normally clean air environment in up to eight (8) distinct locaions.

gas detectors are ideal for use when protection of personnel and property is of concern. Can be used whenever chlorine or sulfur dioxide is unloaded, stored or used.

Highly sensitive, the detector monitors gas levels below OSHA requirements for either chlorine or sulfur dioxide gas.

The seensors respond immediately to the presence of gas, and quickly recover after the gas has cleared. The sensors are also designed to eliminate false alarms caused by interference gases and environmental conditions.

Series 1620B design includes protection against radio frequency / electromagnetic interferences (RFI / EMI) typically present at industrial and municipal plants.

The modular design for the gas detector provides easy installation of the receiver and sensor modules.


       Multi Point Gas Detector Series - 1620B

  • Chlorine or sulfur dioxide gas detection
  • Monitors 1 to 8 locations
  • Maintenance-free, long-life sensor
  • Front panel setup and control
  • Internal annunciator
  • RFI / EMI protection

      

  • Technical Data
    Receiver  
    Power Requirements : 120 or 240 Vac, 50/60 Hz, single phase
    Power consumption 24 watts
    Sensors 1-8
    Input from sensors 4-20 mAdc
    Output to sensors 18-24 Vdc
    LED indicators Power, Ready, Alarm, Malfunction, Numerical Sensor Indicator, Bar Graph Indicator
    Bar graph indicator range 0-10 ppm
    Alarm and Malfunction Contact Rating 10 amps @240 Vac
    Enclosure NEMA 4X (CSA approved available)
       
    Sensor  
    Type Electrochemical of the micro-redox type
    Gases sensed chlorine or sulfur dioxide
    Minimum detectable Concentration 0.5 by volume
    Maximum separation between receiver and sensor 1000 ft (305m)

     

 


This website is best viewed in 1024 x 768 resolution. Powered By WISUALIT